This IO module is used with DDCs to convert an analogue control output to a staged, reverse staged or sequenced relay output. LEDs indicate correct operation and low current draw from 0-10Vdc controller means that the IOR6 can work successfully with most BEMs controllers.
Input Signal: | 0-10Vdc 1mA
min. into 22kΩ impedance |
Output Contacts: | 8A at 230Vac
(resistive load) |
Power Supply: | 24Vac ± 15% @
50Hz or 24Vdc +15%/-6%, 90mA max. |
Hysteresis: | ± 0.2Vdc
about switching points (± 0.1Vdc in binary) |
Operating Modes: | Staged,
Reverse Staged, Sequenced |
Manual Override: | On/Off/Auto
jumper selectable |
Electrical Terminals: | Rising cage
connectors for 0.5-2.5mm² wire. |
Operating Temp.: | -10°C to +40°C,
RH 0-80% non-condensing |
Dimensions: | 52(H) x 116(W) x 83(D)mm |